Advanced Search
XIE Huifan, MEI Yong, ZHOU Jian, XU Guanghu, HUANG Lei, LI Ming, ZHAO Xiaobin, YANG Jian. Optimization of Generator Arrangement for Jin-Zhong HVDCJ. Electric Power, 2020, 53(10): 180-186. DOI: 10.11930/j.issn.1004-9649.201805153
Citation: XIE Huifan, MEI Yong, ZHOU Jian, XU Guanghu, HUANG Lei, LI Ming, ZHAO Xiaobin, YANG Jian. Optimization of Generator Arrangement for Jin-Zhong HVDCJ. Electric Power, 2020, 53(10): 180-186. DOI: 10.11930/j.issn.1004-9649.201805153

Optimization of Generator Arrangement for Jin-Zhong HVDC

  • The paper proposes an optimization method which gives the minimum on-service generator number during the low-water and low-load period on the basis that the power system is safe and stable. The optimization considers three aspects, effective short circuit ratio, stability under island mode and low-order resonance. It is found that the introduction of active DC blocking during isolated operation mode can help effectively eliminate the risk of shortage of short-circuit current, power oscillations and low-order resonance. Operational practice suggests that the minimum on-service generator number of Liyuan and Ahai power plants can be reduced to two respectively when the proposed approach is applied. By reducing the on-service generator number, the risk of having generators operate without load during the low-water and low-load period is alleviated substantially, thus ensuring the safety of equipment of power plants during island mode.
  • loading

Catalog

    Turn off MathJax
    Article Contents

    /

    DownLoad:  Full-Size Img  PowerPoint
    Return
    Return